Aleksandr Sidorov
← All projects

Process control architecture for the utilities of a gas-chemical complex

23 plant units, over 54,000 physical I/O and 1.5 million tags on a fully Russian control platform.

AstraRegulRegul R500DCS/ESD1.5M tagsCritical infrastructure
Years2024–2026
ClientUtilities and offsites of the Baltic Chemical Complex (BCC); NS Digital (NGI LLC, Neftservisholding group) as general subcontractor to IRIS LLC
LocationUst-Luga, Leningrad region, Russia
RoleProcess control system architect
Top level · data centredomain A, AstraRegulTop level · DR sitedomain B, AstraRegulRTsim simulator · Kolibri HART device management · unified diagnosticsRedundant Eltex MES network · MLAG · VLAN · ACLRegul R500unit DCSRegul R500SESD and F&GLocal control systemsRussian and Chinese vendors23 units: boiler houses and heat points · water intake and treatmentnitrogen-air plant, gas station, substations · laboratory and stores> 54,000 physical I/O · > 1.5 million tags
Utilities control architecture: top level in the data centre and DR site, redundant network, unit controllers

Challenge

Bring 23 utility units — boiler houses, river water intake and treatment, nitrogen and air plant, substations, central control room, laboratory and stores — built by several software teams and package vendors into one system. Every component had to be on the Russian registries required for critical information infrastructure.

Solution

The AstraRegul platform with a two-level architecture and a multi-server Astra.Enterprise licence, two domains on geographically separated sites, Regul R500 controllers for DCS and R500S for ESD and fire and gas at the units, plant-wide emergency shutdown from the central control room. DCS, local control, F&G, ESD, technical and commercial energy metering; integration of local control systems from Russian and Chinese vendors; unified diagnostics of PLCs, servers, workstations and switches over hard-wired I/O, HART, OPC UA/DA, SNMP and IEC 60870-5-104; HART field-device management on Kolibri; an RTsim operator training simulator.

My part

System architecture and technical decisions. A document set binding on every contractor: frozen versions of the development environment and libraries, standard blocks for motors, valves and PID loops, 1oo1–2ooN voting with degradation and override rules, a tagging policy, one HMI and role model, standard OS, network and security settings. Review of every subcontractor's work against these rules.

Outcome

Operators and maintenance engineers see the same logic and the same interface on every unit, whoever built it. The system is sized for over 1.5 million tags and 54,000 physical I/O.